As an ENERGY STAR
®
Partner, U.S. Boiler Company has determined that this boiler meets the ENERGY
STAR
®
guidelines for energy efficiency established by the United States Environmental Protection Agency (EPA).
INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
ESC
ENHANCED SEALED COMBUSTION
Gas - Fired Boiler
102601-01 - 4/11
For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide
Boiler Model Number and Serial Number as shown on Rating Label.
Boiler Model Number
ESC
Boiler Serial Number Installation Date
Heating Contractor Phone Number
Address
9700609
Price - $5.00
Vista de página 0
1 2 3 4 5 6 ... 63 64

Resumo do Conteúdo

Página 1 - SERVICE INSTRUCTIONS FOR

As an ENERGY STAR® Partner, U.S. Boiler Company has determined that this boiler meets the ENERGY STAR® guidelines for energy efficiency established

Página 2 - WARNINGS FOR THE INSTALLER

104-c4. CONNECT VENTING (continued)(3) Install vent piping.(4) When conguring the ESC for Power Vent (indoor combustion air) install a 45°

Página 3

115. CONNECT GAS PIPING Size gas piping according to Appendix C – Gas Piping SHUT OFF GAS SUPPLY before servicing the boiler. ALL GAS

Página 4

126. Connect the system supply to the open end of the manifold "S" using a 1¼” male NPT tting.7. Screw an installer-supplied 1¼” pipe or

Página 5 - SPECIFICATIONS

137. CONNECT ELECTRICAL WIRING7-a DISCONNECT ELECTRICAL POWER to the boiler and heating system before servicing. Positively assure that

Página 6 - SPECIFICATIONS (continued)

148. PROGRAM THE CONTROLSUsing IQ Boiler Control DisplayViewing the Operating Mode OptionsIn operating mode the user may view (but not change) boiler

Página 7 - BOILER QUICK-START

158. PROGRAM THE CONTROLS (continued)Unit DisplayORSample Display1 sec1 sec1 secPlease note that in operating mode to hold the display on the value t

Página 8 - 2. POSITION THE BOILER

169. CHECK FOR GAS AND WATER LEAKS GAS LEAKS may result in re or explosion. WATER LEAKS may cause extensive property dam

Página 9 - 4. CONNECT VENTING

1710. PERFORM STARTUP CHECKS AND ADJUSTMENTS10-b FAILURE TO PERFORM THESE CHECKS of the boiler's combustion and safety systems may

Página 10

18ANNUAL MAINTENANCE CHECKLIST WARNINGSTHE BOILER CONTAINS REFRACTORY CERAMIC FIBER, a possible human carcinogen.USE A NIOSH APPROVED RESPIRATOR whe

Página 11 - 5. CONNECT GAS PIPING

19TROUBLESHOOTINGIQ Boiler Control Status Codes (when "Err" is not displayed)Display Status Boiler / Control Action(s)BlankBoiler and Circul

Página 12 - Item Description Part Number

2FOLLOW ALL INSTRUCTIONS and warnings printed in this manual and posted on the boiler.INSPECT THE BOILER ANNUALLY. To keep your boiler safe and efcie

Página 13 - 7. CONNECT ELECTRICAL WIRING

20TROUBLESHOOTING (continued)If "Err" IS displayed on the IQ Boiler Control: "Err" ashes on the IQ Boiler control display follow

Página 14 - 8. PROGRAM THE CONTROLS

21TROUBLESHOOTING (continued)If IQ Boiler Control Shows Status Code “STA 15": The IQ Boiler Control is “Waiting for Limit to Close” and the dis

Página 15 - Unit Display

22REPAIR PARTSKey No.Description[Quantity] Part Number ESC3 ESC4 ESC5 ESC6 ESC7 ESC8 ESC91A Block Assembly 102287-03 102287-04 102287-05 102287-06 102

Página 16

23Key No.Description[Quantity] Part Number ESC3 ESC4 ESC5 ESC6 ESC7 ESC8 ESC92ACanopy Assembly - Sea Level 102594-03 102594-04 102594-05 102594-06 102

Página 17

24REPAIR PARTS (continued)Key No.Description[Quantity] Part Number ESC3 ESC4 ESC5 ESC6 ESC7 ESC8 ESC93A Base Wrapper 71807031 71807041 71807051 718070

Página 18 - WARNINGS

25REPAIR PARTS (continued)Key No.Description[Quantity] Part Number ESC3 ESC4 ESC5 ESC6 ESC7 ESC8 ESC94AGas Valve (Natural Gas), Honeywell VR8204P11718

Página 19 - TROUBLESHOOTING

26REPAIR PARTS (continued)Key No.Description[Quantity] Part Number ESC3 ESC4 ESC5 ESC6 ESC7 ESC8 ESC95A Air Box Assembly 61807032 61807042 61807052 61

Página 20 - TROUBLESHOOTING (continued)

27REPAIR PARTS (continued)Key No.Description[Quantity] Part Number ESC3 ESC4 ESC5 ESC6 ESC7 ESC8 ESC96A IQ Boiler Control 102290-016B IQ Option Panel

Página 21

28Key No.Description[Quantity] Part Number ESC3 ESC4 ESC5 ESC6 ESC7 ESC8 ESC97A Jacket Left Side Panel 102566-017B Jacket Right Side Panel 102567-017C

Página 22 - REPAIR PARTS

29REPAIR PARTS (continued)Key No.Description[Quantity] Part Number ESC3 ESC4 ESC5 ESC6 ESC7 ESC8 ESC98A Water Manifold 806070018B Temperature/Pressure

Página 23 - REPAIR PARTS (continued)

3Special Installation Requirements for MassachusettsA. For all side wall horizontally vented gas fueled equipment installed in every dwelling, buildi

Página 24

30INTERNAL WIRING Figure IW-1: Wiring Diagram

Página 25

31INTERNAL WIRING (continued)Figure IW-2: Wiring Diagram

Página 26

32Figure IW-3: Single Zone System with Domestic Hot Water TankFigure IW-4: Multiple Zone System with Zone CirculatorsINTERNAL WIRING (continued)

Página 27

33Figure IW-5: Multiple Zone System with Zone ValvesFigure IW-6: Multiple Zone System with Zone Circulator PanelINTERNAL WIRING (continued)

Página 28

34T STAT 1VALVE 1T STAT 2VALVE 2T STAT 3OFFONZONE 4 PRIORITYTACO ZVC 404 (OR EQIV.)FOUR ZONE ZONE VALVE CONTROLWITH OPTIONAL PRIORITYTHERMOSTATBOILER

Página 29

35APPENDIX A – COMBUSTION AIR PROVIDE ENOUGH AIR to ventilate the boiler room, dilute the ue gases, and sustain combustion. Ignition fail

Página 30 - INTERNAL WIRING

36APPENDIX B – VENTING VENT THIS BOILER according to the instructions. Failure to do so may cause products of combustion to enter the buil

Página 31 - INTERNAL WIRING (continued)

37APPENDIX B1 INTENTIONALLY OMITTED

Página 32

38APPENDIX B2 – DIRECT VENTINGPlanning a Direct Vent System1. Avoid contact with plumbing or electrical wires.2. Horizontal vent pipe must maintai

Página 33

399. Locate the combustion air terminal on the same face of the building as the vent termination to prevent nuisance boiler shutdowns.10. If the vent

Página 34

4Congratulations on your purchase of a new ESC™ boiler—designed and constructed to provide you with years of reliable service. • ENERGY STAR™ effici

Página 35 - APPENDIX A – COMBUSTION AIR

40Special Instructions for Stainless Steel Direct Vent USE STAINLESS STEEL VENTING only with boilers approved for use with stainless ste

Página 36 - APPENDIX B – VENTING

41Combustion Air (PVC shown) Vent (stainless special gas vent)90° elbow(s) PVC 90° elbow(s) Quantity = x 5’ = equiv. ft. a. Quantity = x 5’ = equiv. f

Página 37

42Figure B-4: Separate Horizontal Air Intake Terminal InstallationFigure B-5: Optional Separate Horizontal Vent Terminal Installation(1) Insert the

Página 38

43APPENDIX B2 – Direct Venting (continued)Special Instructions for Stainless Steel Direct Vent (continued)6. Install the intake air terminal suppli

Página 39

44Figure B-7: Vertical Vent/Air Termination Details for Stainless Steel Direct VentExtend Vent/Air Intake Piping to maintain minimum vertical (“X”) a

Página 40

45Figure B-8: Vertical Air Intake Piping for Direct VentingAPPENDIX B2 – Direct Venting (continued)Special Instructions for Stainless Steel Direct

Página 41

46APPENDIX B3 – POWER VENTINGSome direct vent boilers are also approved with use of indoor combustion air. If the boiler you are installing is appro

Página 42

47 ASSURE GAS PIPING IS LEAK FREE AND OF PROPER SIZE and type for the connected load. SHUT OFF MAIN GAS SUPPLY prior to i

Página 43

48APPENDIX D – SYSTEM PIPING USE PROPER DESIGN AND INSTALLATION PRACTICES and observe all local codes when installing system piping. Pro

Página 44

49APPENDIX D – System Piping (continued)7. Condensation(1) Do not over-pump. Adhere to the design ow requirements for each zone.(2) Adhere to th

Página 45

5ESC SeriesBoiler Model Input (MBH) Output (MBH)Net I=B=R Water (MBH)AFUE (%)ESC3 70 60 52 85.5ESC4 105 90 78 85.4ESC5 140 120 104 85.3ESC6 175 150 13

Página 46 - APPENDIX C – GAS PIPING

50Figure D-0: Piping Schematic SymbolsAPPENDIX D – System Piping (continued)

Página 47

51Figure D-W1: Water Boiler, Series LoopAPPENDIX D – System Piping (continued)Figure D-W2: Water Boiler, Two or More Zones

Página 48 - APPENDIX D – SYSTEM PIPING

52Figure D-W3: Water Boiler, Tankless Coil, Two or More ZonesAPPENDIX D – System Piping (continued)Figure D-W4: Water Boiler, Indirect Water Heater,

Página 49

53APPENDIX D – System Piping (continued)Figure D-W5: Water Boiler, Indirect Water HeaterFigure D-W6: Multiple Water Boilers, Indirect Water Heater,

Página 50

54APPENDIX E – FILLING THE SYSTEM AND CHECKING FOR LEAKSFill entire heating system with water and vent air from system. Use the following procedure o

Página 51

55APPENDIX F – ADJUSTING GAS INPUT RATENatural Gas Boilers:1. Turn off gas supply to all appliances other than gas-red boiler.2. Note the rated man

Página 52

56APPENDIX F – Adjusting Gas Input Rate (continued)Seconds for Two (2) RevolutionsSize of Gas Meter DialOne-Half Cu. Ft.OneCu. Ft.TwoCu. Ft.24 150.0 3

Página 53

57APPENDIX G – CHECKING DRAFT AND COMBUSTIONCHECK DRAFT (GAS BOILERS WITH DRAFT HOODS)1. Insofar as is practical, close all doors and windows in the

Página 54

58APPENDIX H – IQ CONTROL SYSTEMIQ Control System Overview The “IQ Control System” consists of an IQ Boiler Control and an IQ Option Panel with option

Página 55

59APPENDIX H – IQ Control System (continued)IQ Outdoor Reset Option Card: P/N 102723-01 Installing the IQ Outdoor Reset Option Card is the simplest

Página 56

6Figure S-1: Minimum Clearances to CombustiblesSPECIFICATIONS (continued)

Página 57

60APPENDIX H – IQ Control System (continued)IQ High Limit Option Cards add auxiliary temperature limit-rated controls to ESC Boilers. High Limit Opti

Página 58

61APPENDIX H – IQ Control System (continued)Optional ComponentsSystem Parts ListPart Number Item Description102723-01Outside Reset IQ Option Card, Dom

Página 59

62SERVICE RECORDDATE SERVICE PERFORMED

Página 60

63SERVICE RECORDDATE SERVICE PERFORMED

Página 61 - Additional Information List

64U.S. Boiler Company, Inc.P.O. Box 3020Lancaster, PA 17604(717) 397-4701www.usboiler.burnham.com

Página 62 - SERVICE RECORD

7Installation: 1. Unpack the crate ... 8 2. Position t

Página 63

8 THE BOILER IS TOP-HEAVY. Do not allow it to tip over.1. Remove the sleeve. 2. Remove the contents from the skid, except the boiler.

Página 64 - (717) 397-4701

93. PROVIDE COMBUSTION AIR INSUFFICIENT COMBUSTION AIR SUPPLY may result in the production and release of deadly carbon monoxide (CO) i