103698-02 - 10/12
Price - $5.00
INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
Series 2
®
Gas - Fired Boiler
,reliobnonoitamrofnignikeesnehW.rotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
.lebaLgnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp
rebmuNledoMrelioB
rebmuNlaireSrelioB
etaDnoitallatsnI
2
rotcartnoCgnitaeH
rebmuNenohP
sserddA
9700609
9700609
Vista de página 0
1 2 3 4 5 6 ... 55 56

Resumo do Conteúdo

Página 1 - Series 2

103698-02 - 10/12Price - $5.00INSTALLATION, OPERATING ANDSERVICE INSTRUCTIONS FORSeries 2®Gas - Fired Boiler,reliobnonoitamrofnignikeesnehW.rotcartnoc

Página 2

10IV. BOILER WATER PIPING (continued)Figure 5: Recommended Water Piping for Zone Valve Zoned Heating Systems

Página 3

11IV. BOILER WATER PIPING (continued)Figure 6: Recommended Water Piping for Circulator Zoned Heating Systems

Página 4

12IV. BOILER WATER PIPING (continued) There are many possible causes of oxygen contamination such as:a. Addition of excessive make-up water as a re

Página 5 - (CONTINUED)

134. Piping and ttings required to install LWCO are eld supplied.5. When constructing a piping tree to install LWCO select ttings (tees, elbows e

Página 6

14Figure 10: Blocked Vent SwitchInstallation DiagramA. INSTALL DRAFT HOOD without modication on outlet of ue collector (See Figure 1). Secure wi

Página 7

15Figure 11: Plug-in Damper Installation 1. The vent damper must be the same size as the outlet of the Draft Hood supplied with the boiler (see Figur

Página 8 - III. GAS PIPING

16Figure 12: Typical Vent Installation 6. Vent pipe to chimney must not be smaller than outlet on draft hood or damper. Although single wall vent pip

Página 9 - IV. BOILER WATER PIPING

17 Au moment du retrait d’une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil toujours raccordé au système d’evac

Página 10

18A. INSTALL A ROOM THERMOSTAT on an inside wall about four feet above oor. Never install thermostat on an outside wall or where it will be inu

Página 11

19Figure 13: Connection Wiring Diagram, Intelligent Hydronic ControlVI. ELECTRICAL (continued)

Página 12

2NOTE: The equipment shall be installed in accordance with those installation regulations in force in the area where the installation is to be made.

Página 13

20Figure 14: Ladder Wiring Diagram, Intelligent Hydronic ControlVI. ELECTRICAL (continued)

Página 14 - V. VENTING

21Figure 15: Wiring Schematic, Zone ValvesFigure 16: Wiring Schematic, Zone CirculatorsVI. ELECTRICAL (continued)

Página 15 - V. VENTING (continued)

22VII. START-UP AND CHECKOUTA. MAIN BURNER CHECK - Check main burners to see that they were not dislodged during shipment. Rear of burners should

Página 16

23Figure 19: Operating Instructions, VR8204 and VR8304 Gas ValvesVII. START-UP AND CHECKOUT (continued)

Página 17

24C. CHECK GAS INPUT RATE TO BOILERNOTICE USA boilers built for installation at altitudes greater than 2,000 feet above sea level have been spe

Página 18 - VI. ELECTRICAL

25VII. START-UP AND CHECKOUT (continued)E. CHECK PILOT BURNER FLAME.See Figure 22. The pilot produces three (3) ames. The center ame should b

Página 19 - VI. ELECTRICAL (continued)

26VIII. OPERATIONA. BOILER SEQUENCE OF OPERATIONNORMAL OPERATION1. The Series 2 Boilers are equipped with an Intelligent Hydronic Control (control)

Página 20

27VIII. OPERATION (continued)The control display, along with Up ñ, Down ò, and “I” keys may be used to view boiler operating status (Figure 24). D.

Página 21

28VIII. OPERATION (continued)E. CHANGING THE ADJUSTABLE PARAMETERS To adjust parameters such as High Limit Setpoint and High Limit Differential:1.

Página 22 - VII. START-UP AND CHECKOUT

29VIII. OPERATION (continued)7. Domestic Hot Water (DHW) Terminal Function (dh_) The control allows conguration of the DHW Circulator output functi

Página 23

3WARNINGThis boiler requires regular maintenance and service to operate safely. Follow the instructions contained in this manual.Improper installatio

Página 24

30IX. SERVICE AND MAINTENANCEA. Inspection should be conducted annually. Service as frequently as specied in paragraphs below. While service or mai

Página 25

31i. Brush top of burners with a soft bristle brush, see Figure 26. Vacuum burners. Check orices to see that drilled passageways are free of lint

Página 26 - VIII. OPERATION

32Important Product Safety InformationRefractory Ceramic Fiber ProductWarning:The Repair Parts list designates parts that contain refractory ceramic f

Página 27 - VIII. OPERATION (continued)

33X. TROUBLESHOOTINGA. BEFORE TROUBLESHOOTING The following pages contain trouble shooting tables for use in diagnosing control problems. When us

Página 28

34X. TROUBLESHOOTING (continued)Display Status Recommended Corrective ActionBlank Boiler or Control is not poweredNo 120 Vac Power at boiler, check b

Página 29

35C. USE STA (STATUS) NUMBER TO GUIDE TROUBLESHOOTING The control will ash “STA” followed by a number. Use this number to identify the boiler pro

Página 30 - IX. SERVICE AND MAINTENANCE

36X. TROUBLESHOOTING (continued)6. Circulator is On, Damper is Open But Boiler Fails to Start Display / Status DescriptionSTA 10Retry / RecycleDela

Página 31 - G. LUBRICATION

37Display / StatusRecommended Corrective ActionStA 10Retry / Recycle DelayStA 13Soft Lockout1. No Spark a. Can you hear sparking while STA 6 is

Página 32

38XI. REPAIR PARTSSection Assembly and Canopy Group ...38Base Assembly ...

Página 33 - X. TROUBLESHOOTING

39Key No.Description Part No.Quantity202 202X 203 204 205 206 207 208 209 2101. Section Assembly1 Section Assembly, Complete103918-02 1 --- --- --- -

Página 34

4TABLE OF CONTENTSI. Product Description, Specications and Dimensional Data... 4II. Pre-Installation & Boiler Mounting ...

Página 35

40XI. REPAIR PARTS (continued)Base AssemblyKey No.DescriptionBoiler SizePart No. Qty.3. Base Assembly3Base Assembly(Complete)Available for 1 Inch B

Página 36

41XI. REPAIR PARTS (continued)Key No.DescriptionBoiler SizePart No. Qty.3. Base Assembly Continued3CBase Front PanelAssembly202 618600241 1202X 618

Página 37 - Recommended Corrective Action

42Manifold and Main Burners(1 Inch Main Burners)XI. REPAIR PARTS (continued)

Página 38 - XI. REPAIR PARTS

43XI. REPAIR PARTS (continued)Key No.Description Part No.Quantity202 202X 203 204 205 206 207 208 209 2104. Manifold and Main Burners (1 Inch Main B

Página 39 - XI. REPAIR PARTS (continued)

44Manifold and Main Burners(40mm Main Burners) XI. REPAIR PARTS (continued)Key No.Description Part No. Quantity203 202X 204 205 206 207 208 209 2104.

Página 40

45XI. REPAIR PARTS (continued)Key No.Description Part No.Quantity202X 203 204 205 206 207 208 209 2104. 40 MM Main Burners Only (Continued)4C. 40

Página 41

46XI. REPAIR PARTS (continued)Key No.Description Part No.Quantity202 202X 203 204 205 206 207 208 209 2105. Pilot Burner and Gas Valve, Natural Gas5

Página 42

47XI. REPAIR PARTS (continued)Key No.Description Part No.Quantity202 202X 203 204 205 206 207 208 209 2106. Jacket Assembly, Complete6 Jacket Assemb

Página 43

48XI. REPAIR PARTS (continued)Jacket Assembly

Página 44

49XI. REPAIR PARTS (continued)Key No.Description Part No.Quantity202 202X 203 204 205 206 207 208 209 2106. Jacket Assembly (Continued)6B Jacket Ves

Página 45

5I. PRODUCT DESCRIPTION, SPECIFICATIONS AND DIMENSIONAL DATA (CONTINUED)Figure 1: Line DrawingBoiler Model NumberDimensions [Inches] Gas Connection

Página 46

50Water TrimXI. REPAIR PARTS (continued)

Página 47

51Key No.Description Part No. Quantity7Safety Relief Valve, 30 psi, 3/4 NPT, Conbraco 10-408-05 81660319 1Safety Relief Valve, 50 psi, 3/4 NPT, Conbra

Página 48

52Key No.Description Part No. Quantity12. Transformer/J-Box/Controls12A Junction Box, 4" x 4" x 1-1/2" 8136259 112B Junction Box Cove

Página 49

53XI. REPAIR PARTS (continued)Draft HoodKey No.Description Part No.Quantity202 202X 203 204 205 206 207 208 209 21016. Draft Hood Carton16 Draft Hoo

Página 50

54Figure NumberPage Number DescriptionSection I - Product Description, Specications & Dimensional DataFigure 1 5 Lin

Página 51

55TableNumberPage Number DescriptionSection III - Gas PipingTable 1 8 Maximum Capacity of Schedule 40 Pipe in CFH for Nat

Página 52

56U.S. Boiler Company, Inc.P.O. Box 3020Lancaster, PA 176041-888-432-8887www.usboiler.net

Página 53

6II. PRE-INSTALLATION AND BOILER MOUNTINGWARNINGIf you do not follow these instructions exactly, a re or explosion may result causing propert

Página 54 - APPENDIX A - FIGURES

7a. CLOSET INSTALLATIONS (conned space) in a building of other than unusually tight construction (see denition below), provide combustion and vent

Página 55 - APPENDIX B - TABLES

8III. GAS PIPINGA. CONNECT GAS SERVICE from Meter to gas control assembly in accordance with Local Piping Codes and requirements of Gas Company. T

Página 56 - 1-888-432-8887

9A. BOILER WATER PIPINGCAUTIONFailure to properly pipe boiler may result in improper operation and damage to boiler or building.1. CLEARANCES - Hot